The GCS type low-voltage withdrawable switchgear (hereinafter referred to as the device) is a new type of low-voltage withdrawable switchgear designed based on the principles of safety, economy, reasonableness and reliability. The product has the characteristics of high breaking and making capacity, good dynamic and thermal stability, flexible and easy combination of electrical solutions, strong serialization and practicality, novel structure, and high protection level. It can be used as a replacement product for low-voltage withdrawable switch cabinets. The device complies with IEC439-1 "Low-voltage complete sets of switchgear and control equipment", GB7251 "Low-voltage complete sets of switchgear and equipment and control equipment" and other standards.
use
This device is suitable for power distribution systems in power plants, petroleum, chemical industry, metallurgy, textiles, high-rise buildings and other industries. In large power plants, petrochemical systems and other places with a high degree of automation that require computer interfaces, it can be used as a three-phase AC frequency of 50 (60 )Hz, a low-voltage complete power distribution device used for power distribution, motor centralized control, and reactive power compensation in power generation and power supply systems with a rated operating voltage of 380V (400V) and (660V) and a rated current of 4000A and below .Model and meaning
Conditions of use
a. The ambient air temperature is not higher than +40°C and not lower than -5°C. If the average temperature within 24 hours is not higher than +35°C, the equipment must be derated according to actual conditions when operating above the above ambient temperature;
b. For indoor use, the altitude of the use location shall not exceed 2000m
c. Relative humidity of the surrounding air It should not exceed 50% when the maximum temperature is +40°C. A larger relative humidity is allowed at lower temperatures, such as 90% at +20°C. It should be considered that condensation may occasionally occur due to temperature changes. Influence;
d. When the device is installed, the inclination with the vertical plane does not exceed 5%, and the entire cabinet row is relatively flat (in compliance with GBJ232 standards);
e. The device should be installed in a location that is free from severe vibration and impact and is not sufficient to expose electrical components to undue stress. Corrosive places;
f. When users have special requirements, they can negotiate with the manufacturer.
Technical parameters
project | unit | parameter | |
Rated insulation voltage | V | Communication 660(1000) | |
Rated working voltage | Main circuit | V | Communication 380(660) |
Auxiliary circuit |
AC 380,220,24 DC 220,110 |
||
Rated frequency | Hz | 50(60) | |
Horizontal bus rated current | A | ≤4000 | |
Vertical busbar rated current | A | 1000 | |
Rated peak withstand current | KA | 105(176) | |
Rated short-time withstand current | KA | 50(80) |
The main frame of the device is made of 8MF steel. The frame adopts two structural forms: assembly and partial connection. There are mounting module holes E=20mm on the main frame.
The functional rooms of the device are strictly separated. The compartments are mainly divided into functional unit rooms and busbar rooms. The functions of each unit are relatively independent.
The device does not adopt the traditional design of placing the horizontal main busbar on the top of the cabinet, so that there are outlet channels above and below the cable room. It solves the problem of old products not being able to go offline.
The size series of the device cabinet are as follows:
Technical parameters
Height(mm) | Width(mm) | Depth(mm) |
220 | 400 | 800 |
1000 | ||
600 | 800 | |
1000 | ||
800 | 600 | |
800 | ||
1000 | ||
1000 | 600 | |
800 | ||
1000 |
After the product arrives at the delivery location, you should first check whether the packaging is intact and intact. If any problems are found, you should promptly notify the relevant contract department to keep business records and jointly analyze the reasons. Take care of the visa and aftermath arrangements. Products that are not to be installed immediately should be placed in an appropriate place and properly stored according to normal usage conditions or temporary storage regulations for electrical equipment.
The installation of the product should be carried out according to the installation diagram (see attached picture). The basic steel and bolts used for bolting are provided by the user. When connecting the main busbars, if the surface is uneven due to transportation, storage, etc., it should be flattened before connection and tightening.
Product completeness
The manufacturer should provide the following documents and attachments when supplying goods:
a. Packing list;
b. Product certificate;
c. Instructions for use;
d. Factory test report;
e. Relevant electrical drawings;
f. Cabinet door keys, operating handles and contracts Specified spare parts;
g. Installation and operating instructions for main electrical components.
Ordering Instructions
a. All models of the product include main circuit plan number and auxiliary circuit plan number;
b. Main circuit system combination sequence diagram;
c. Auxiliary circuit electrical schematic diagram;
d. List of components in the cabinet;
e. Voltage and current in the circuit , time and other setting parameters;
f. Other special requirements that are inconsistent with the normal use of the product.